HS Code:
39100000
Technical Data
Typical values, not a specification. The technical data sheet (TDS) is binding.
Processing
- Viscosity of Mixture
- 50 mPa·s
Physical and thermal
- Density (23 °C)
- 0.97 g/cm³
- Temperature resistance (duration)
- -50 to 200 °C
- Peak temperature (briefly)
- 200 °C
- Flash point
- 250 °C
Storage
- Shelf life in original packaging
- 24 months
- Storage Temperature
- -20 to 50 °C
Product Information
- Brand
- Bluesil
- Manufacturer
- Elkem Silicones
- Container
- 1kg, 5kg, 25kg, 200kg, 1000kg
- Number of components
- 1K (one-component)
- Consistency
- Flowable
- Mixing Ratio
- One-component
Further Properties
- UV resistance
- Yes
Physical Properties
- Cured Color
- Transparent
- Self-leveling
- Yes
- Viscosity (cSt)
- 50 cSt
- Density (g/cm³)
- 0.960 g/cm³
Electrical Properties
- Electrical Insulation
- Yes
Product Approvals
- Food contact
- No
- Medical grade
- No
Thermal Properties
- Flash point (°C)
- 280 °C
- Pour point (°C)
- -55 °C
Product Description
BLUESIL FLD 604V50: Insulating and cooling fluid
BLUESIL FLD 604V50 is a dielectric fluid made of polydimethylsiloxane. Its purity is tested for electrotechnical applications. The manufacturer describes it as an insulating and cooling medium for immersed transformers and other medium-voltage equipment.
Typical manufacturer values
- Kinematic viscosity: approx. 50 mm²/s at 25 °C.
- Density: approx. 0.96 kg/dm³ at 20 °C according to the safety data sheet.
- Flash point: 280 °C according to AFNOR NF T 60 118.
Viscosity and flash point refer to technical data sheet no. 976-V2 dated June 1, 2023. Electrical testing depends, among other things, on the measurement method and electrode geometry.
Fire protection and system conditions
The manufacturer's data sheet describes the fire behavior and test conditions in separate tables. Approval for a specific transformer installation requires an assessment of the entire assembly. A high flash point does not imply general non-flammability.
Moisture and impurities affect the dielectric properties. Therefore, filling, material compatibility, sealing, and fluid monitoring must be determined according to the system specifications and the manufacturer's documentation. Any leakage must be contained; the safety data sheet and operational safety measures must be observed.
BLUESIL FLD 604V50 – Technical Data Sheet EN · Discuss system conditions and required documents